This is taken directly from Snap7 documentation: http://snap7.sourceforge.net/
|
||||
|
||||
## S7 1200/1500 Notes
|
||||
|
||||
An external equipment can access to S71200/1500 CPU using the S7 “base” protocol, only working as an HMI, i.e. only basic data transfer are allowed.
|
||||
All other PG operations (control/directory/etc..) must follow the extended protocol, not (yet) covered by Snap7.
|
||||
Particularly to access a DB in S71500 some additional setting plc-side are needed.
|
||||
|
||||
1. Only global DBs can be accessed.
|
||||
2. The optimized block access must be turned off.
|
||||
3. The access level must be “full” and the “connection mechanism” must allow GET/PUT.
|
||||
|
||||
Let’s see these settings in TIA Portal V12
|
||||
DB property
|
||||
Select the DB in the left pane under “Program blocks” and press Alt-Enter (or in the contextual menu select “Properties…”)
|
||||
Uncheck Optimized block access, by default it’s checked.
|
||||

|
||||
|
||||
## Protection
|
||||
|
||||
Select the CPU project in the left pane and press Alt-Enter (or in the contextual menu select “Properties…”)
|
||||
In the item Protection, select “Full access” and Check “Permit access with PUT/GET ….” as in figure.
|
||||
|
||||

|
||||